Launch Image Gallery | | VC-485 Multi-Function Communication Interface
The VC-485 Communication Interface is an RS-232/RS-485 protocol converter primarily used to connect a PC to a KT-100/ KT-200/ KT-300 controller. The maximum bus length is 5 km (18,000 ft, when line repeater is used) and 1,200 m (4,000 ft) for EntraPass when using Ethernet Grade 3, unshielded, two twisted pair cable (Belden # 1227A recommended). Two VC-485's may be connected back-to-back to be used as a line repeater in order to extend the RS-485 communications bus. |
|
|
|
|
|
- Converts RS-232 to RS-485
- Supports up to 32 Kantech controllers
- Uses UTP cable
- Powered by 5 VDC or 12 VDC
- Extends communication up to 1,200 m (4,000 ft)
- Extends communication up to 5,486 m (18,000 ft) by connecting two together
- Two VC-485s may be connected back-toback to extend the RS-485 communication bus
|
No Resources available at this time |
|
|
|
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products include all features. Some features and integrations way require additional licensing options. Availability varies by region and may require certification; please verify conditions with your Regional Sales Manager.
|
|