Unit must be Factory Reset to be able to configure it. Once configured, the Web Page will be disable and the KT-Finder will provide a read only access. WARNING: This reset will clear all IP Link configuration including the IP address.
Factory Default
(DHCP)
Disconnect DC power.
Connect a wire between the PGM1 and IN1
Connect power.
The Heartbeat Patterns should be steady red, then blink very quickly.
Remove jumper when it start flashing.
Remove the wire between PGM1 and IN1.
Heartbeat patterns should now be 1 long flash per sec.
The IP Link will now be in DHCP mode and will attempt to obtain an IP address automatically from the DHCP server.
Factory Default
Static IP
192.168.1.2
Disconnect DC power.
Connect a wire between the PGM1 and IN1
Connect a wire between the PGM2 and IN2
Connect power.
The Heartbeat Patterns should be steady red, then blink very quickly.
Remove jumper when it start flashing.
Hearbeat patterns should now be 3 flashes in 3 secs and OFF for 1 sec.
The IP Link will now be at IP address 192.168.1.2.
Configure the IP Link using either the KT-Finder or the Web Configuration Page.