KT-100 should be Hard Reseted prior to communicate with any EntraPass software
Procedure to perform a Hard Reset: 1. Disconnect the Power Supply. 2. Remove all connections of Z1 (DOOR) and R3 terminals. 3. Place a jumper between the Z1 (DOOR) and R3 terminals. 4. Apply power to the Power Supply.
The VITAL LED should flash 4 times. This means that the controller is in the Hard Reset mode
5. Disconnect the jumper.
|